Simulation Equipment
Name: FKGA23-SH609 Type Data acquisition terminals of special transformer
Details Introduction
FKGA23-SH609 Type Special Acquisition Terminal is the latest product which meets the needs of National Grid 2013. It based on the computer applications technology, modern communication technology, electricity automatic control technology to collect and deal the data, also the real time protection. It combines the electricity load management and the client on-site service in one, having the functions of advanced technology, complete functions, flexible extended. It adopts the high-performance 32 bit (ARM9 series) CPU and Linux operating system, with the functions of data collecting, data saving and processing, remote meter reading, variable parameter measurement, electric energy measuring, alternating current sampling, remote maintenance and software upgrade, abnormal monitoring electricity.
The main technical parameter:
|
Technical standard: |
Q/GDW 1374.1-2013、 |
||||
|
Pulse input |
2 ways,no source,the pulse width resolution 80ms |
||||
|
Control output |
2way relays,contact capacity 250V/5A, |
||||
|
The alarm output |
1way relay,normally open contact,contact capacity250V/5A, |
||||
|
State variable input |
2 way,input for passive open/close switch contact |
||||
|
Meter reading interface |
2independent RS485 interface |
||||
|
Number of meter reading |
64 |
||||
|
Local maintenance interface |
1way infrared;1way RS485;1way USB |
||||
|
Upward communication |
Wireless GPRS |
||||
|
Downward communication |
RS485 |
||||
|
Specification |
Voltage |
3×100V 3×220/380V |
|||
|
Current |
1.5(6)A |
||||
|
Voltage measurement range |
0.7Un~1.2Un |
||||
|
Clock battery |
3.6V,1.2Ah,it can working for more than 10 years if out of power |
||||
|
Power outages backup battery |
4.8V,350mAh,chargeable |
||||
|
AC sampling accuracy |
Voltage |
1.0 class |
Current |
1.0 class |
|
|
Active power |
1.0 class |
Inactive power |
2.0 class |
||
|
Clock error |
≤0.5s/d(23℃) |
||||
|
Checking time error |
≤2s |
||||
|
Operating temperature |
-40℃~+70℃ |
||||
|
Dimension |
290mm×180mm×95mm(L×W×H) |
||||