Standard Test Device

Name: SH-YJ10 Voltage drop and load simulational device

+
  • undefined

Details Introduction


SH-YJ10 by the simulation cabinet, energy meter cabinet, computer, control software, simulation substation voltage transformer, current transformer secondary line and metering system.

Training projects can be completed are: secondary voltage drop and load measurement of high-voltage metering simulation of energy meter field calibration meter reading rotation meter installation meter receiving electricity

The main training programs are: secondary voltage drop and load measurement (including PT secondary voltage drop simulation, PT secondary load simulation, CT secondary load simulation)

Simulation cabinet

1, built-in three-phase program-controlled power supply, able to simulate the secondary output of the transformer

2、Output voltage:

Output range: 3 × 100/57.7 v

Adjustment range: 0~120% continuously adjustable

Each phase voltage amplitude can be set separately

Voltage symmetry can be set arbitrarily

3、Output current:

Current range: 5A

Adjustment range: 0%~120% continuously adjustable

Amplitude of each phase current can be set separately

Phase of each phase current can be set separately

4、Phase adjustment: 0°-359.99°.

5、Frequency adjustment: 45Hz-65Hz

6、Built-in three-phase digital standard meter, real-time display of output voltage and current.

7、Built-in line impedance simulation module, able to imitate 2464200 kinds of impedance combinations

8、Equipped with a transformer terminal block for measurement

9、Equipped with PT insurance for measurement.

Meter cabinet

1, meter cabinet according to the substation metering screen design, configuration of 2 meters

Three-phase three-wire multifunction meter 3 × 100V, 1.5(6)A

Three-phase four-wire multifunction meter 3 × 100/57.7V, 1.5(6)A

2、Equipped with a joint junction box for measurement

3、The cabinet is equipped with voltage and current terminals for measurement.