Standard Test Device
Name: SH-YJ10 Voltage drop and load simulational device
Details Introduction
SH-YJ10 by the simulation cabinet, energy meter cabinet, computer, control software, simulation substation voltage transformer, current transformer secondary line and metering system.
Training projects can be completed are: secondary voltage drop and load measurement of high-voltage metering simulation of energy meter field calibration meter reading rotation meter installation meter receiving electricity
The main training programs are: secondary voltage drop and load measurement (including PT secondary voltage drop simulation, PT secondary load simulation, CT secondary load simulation)
Simulation cabinet
1, built-in three-phase program-controlled power supply, able to simulate the secondary output of the transformer
2、Output voltage:
Output range: 3 × 100/57.7 v
Adjustment range: 0~120% continuously adjustable
Each phase voltage amplitude can be set separately
Voltage symmetry can be set arbitrarily
3、Output current:
Current range: 5A
Adjustment range: 0%~120% continuously adjustable
Amplitude of each phase current can be set separately
Phase of each phase current can be set separately
4、Phase adjustment: 0°-359.99°.
5、Frequency adjustment: 45Hz-65Hz
6、Built-in three-phase digital standard meter, real-time display of output voltage and current.
7、Built-in line impedance simulation module, able to imitate 2464200 kinds of impedance combinations
8、Equipped with a transformer terminal block for measurement
9、Equipped with PT insurance for measurement.
Meter cabinet
1, meter cabinet according to the substation metering screen design, configuration of 2 meters
Three-phase three-wire multifunction meter 3 × 100V, 1.5(6)A
Three-phase four-wire multifunction meter 3 × 100/57.7V, 1.5(6)A
2、Equipped with a joint junction box for measurement
3、The cabinet is equipped with voltage and current terminals for measurement.